G3SeriesPROFIBUS‐DPTechnicalManual
Page 45
TDG3PTTM1-2EN 02/09
Subject to change without notice
www.numatics.com/g3
One Analog Input per Connector - M12 Female Modules
Module
Part No.
Signal Type
Short Circuit
Protection
Input Points
240-212 0-10 VDC
240-214 4-20 mA
YES – Visual 4
Input Mapping
BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
X Input No. 1 Input No. 1 Input No. 1 Input No. 1 Input No. 1 Input No. 1 Input No. 1
Input No. 1
(LSB)
X+1
Input No. 1
(MSB)
Input No. 1 Input No. 1 Input No. 1 Input No. 1 Input No. 1 Input No. 1 Input No. 1
X+2 Input No. 2 Input No. 2 Input No. 2 Input No. 2 Input No. 2 Input No. 2 Input No. 2
Input No. 2
(LSB)
X+3
Input No. 2
(MSB)
Input No. 2 Input No. 2 Input No. 2 Input No. 2 Input No. 2 Input No. 2 Input No. 2
X+4 Input No. 3 Input No. 3 Input No. 3 Input No. 3 Input No. 3 Input No. 3 Input No. 3
Input No. 3
(LSB)
X+5
Input No. 3
(MSB)
Input No. 3 Input No. 3 Input No. 3 Input No. 3 Input No. 3 Input No. 3 Input No. 3
X+6 Input No. 4 Input No. 4 Input No. 4 Input No. 4 Input No. 4 Input No. 4 Input No. 4
Input No. 4
(LSB)
X+7
Input No. 4
(MSB)
Input No. 4 Input No. 4 Input No. 4 Input No. 4 Input No. 4 Input No. 4 Input No. 4
Diagnostic Telegram
BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
X
Allocated
and
Reserved
Allocated
and
Reserved
Allocated
and
Reserved
Allocated
and
Reserved
Power Status
for Conn. D
Power Status
for Conn. C
Power Status
for Conn. B
Power Status
for Conn. A
X+1
High Alarm
for Conn. D
Low Alarm
for Conn. D
High Alarm
for Conn. C
Low Alarm
for Conn. C
High Alarm
for Conn. B
Low Alarm
for Conn. B
High Alarm
for Conn. A
Low Alarm
for Conn. A