Figure 2-34: Variables - Totalizer Tab
Procedure
1. To turn the totalizer functionality on or off, select Start or Stop from the Mode drop
down menu under the Totalizer Setup heading. The totalizer Units may also be
edited under this heading.
2. Verify the Totalized Parameter and the Totalizer Maximum value. To edit the
Totalized Parameter, select the Configure Totalizer button under the Totalizer
Control heading.
Note
When the totalizer reaches its maximum value, it automatically resets to zero and
continues totalizing. The default maximum is a value equivalent to 4.29 billion
pounds, actual cubic feet, or BTU. To edit the Totalizer Maximum value, select the
Set Totalizer Maximum button under the Totalizer Control heading.
3. To reset the Totalized Reading to zero, select the Reset Totalizer button under the
Totalizer Control heading.
4. Under the Custom Units Setup heading, the user may configure a custom unit for
the Totalized Reading. Custom units allow the totalizer rate to be displayed in units
of measure that are not standard in the Rosemount 3051SMV.
Note
If the totalizer rate is configured as the primary variable and is being output via the
4–20 mA signal, verify the 4–20 mA range (LRV and URV) after completing the
custom unit configuration. For more information on verifying the 4–20 mA range,
see Basic device configuration.
Follow these steps to configure a custom unit:
a) Custom Unit: Enter the desired custom unit label to be displayed for the
Totalized Reading. Up to five characters including letters, numbers, and
symbols can be entered in the custom unit field.
Configuration Reference Manual
October 2018 00809-0100-4803
54 Rosemount 3051S Multivariable Transmitter