3.4.2 Configure alarm direction
The transmitter alarm direction is set by repositioning the alarm switch. Position the
switch in the HI position for fail high and in the LO position for fail low. See for more
information on alarm and saturation levels.
3.4.3 Mounting considerations
For dimensional drawing information refer to .
Housing rotation
The housing can be rotated to improve field access to wiring or to better view the optional
LCD display. To rotate the housing, perform the following procedure:
Procedure
1. Loosen the housing rotation set screw.
2. Turn the housing up to 180° to the left or right of its original (as shipped) position.
Note
Do not rotate the housing more than 180° without first performing a disassembly
procedure (see ). Over-rotation may sever the electrical connection between the
sensor module and the feature board.
3. Retighten the housing rotation set screw.
Figure 3-2: Housing
A. Feature board
B.
3
/32-in. housing rotation set screw
LCD display rotation
In addition to housing rotation, the optional LCD display can be rotated in 90° increments
by squeezing the two tabs, pulling out, rotating and snapping back into place.
Note
If LCD display pins are inadvertently removed from the feature board, re-insert the pins
before snapping the LCD display back into place.
Installation
Reference Manual
October 2018 00809-0100-4803
74 Rosemount 3051S Multivariable Transmitter