Reference Manual
00809-0100-4840, Rev. BA
July 2008
F-9
Rosemount 3100 Series
P011 = “Horizontal Cyl Flat” (Horizontal cylinder, flat ends)
This setting is applicable when volume of content measurements involving a
horizontally oriented cylindrical vessel with a constant diameter is required –
See Figure F-4 on page F-9 for a cross-sectional view.
By selecting “Horizontal Cyl”, the live volume of the content is derived from
the raw measured liquid level, the full volume of the ideal cylindrical tank
(P013), and the diameter of that vessel (P014).
Figure F-4. Sphere or Cylindrical
Tank Example
P011 = “Spherical”
This setting is applicable when volume of content measurements involving a
spherical vessel with a constant diameter is required – See Figure F-4 on
page F-9 for a cross-sectional view.
By selecting “Spherical”, the live volume of the content is derived from the raw
measured liquid level and the full volume of the ideal spherical vessel (P013)
Reference (P010).
P013 = Full volume of ideal cylindrical or spherical tank of constant diameter (P014)