Reference Manual
00809-0100-4840, Rev. BA
July 2008
Rosemount 3100 Series
www.rosemount.com
Appendix A Reference Data
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-1
Temperature and Pressure Ratings . . . . . . . . . . . . . . . . . page A-3
Load Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-3
Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-4
Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-6
Spare Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-9
SPECIFICATIONS
General
Product Rosemount 3100 Series liquid level transmitters:
Rosemount 3101: Level and Distance measurement.
Rosemount
3102: Level, Distance, Volume, Open channel flow measurement, two integral signal relays.
Rosemount 3105: Level, Distance, Volume, Open channel flow measurement for hazardous locations.
Measurement principle Ultrasonic, time-of-flight.
Measuring performance
Measurement range Rosemount 3101: 1 to 26 ft (0,3 to 8 m)
Rosemount 3102: 1 to 36 ft (0,3 to 11 m)
Rosemount 3105: 1 to 36 ft (0,3 to 11 m)
Level resolution Better than
1
/16 in. (1 mm)
Level accuracy The 3101: ± 0.2 in. (5 mm) for <3.3 ft (1 m),
± 0.5% of measured distance for > 3.3 ft (1 m)
The 3102 and The 3105: ± 0.1 in. (2.5 mm) <3.3 ft (1 m),
±0.25% of measured distance for > 3.3 ft (1 m)
under reference conditions
(1)
Blanking distance (Dead Zone) 12 in.(0,3 m)
Update interval 1 second
Display / Configuration
Integral Display 4/5 digit display for live measurement, and for configuration purposes.
Output Units For Level or distance-to-surface: m, ft, in, or none
For Contents: l, m
3
, gal, or ft
3
For Flow: l/s, l/m, m
3
/hr, gal/s, gal/m, ft
3
/m (cfm), ft
3
/hr, or none
Output Variables Rosemount 3101: Level, or distance-to-surface
Rosemount 3102: Level (or distance-to-surface), Content (Volume), and Flow.
Rosemount 3105: Level (or distance-to-surface), Content (Volume), and Flow.
Configuration tools Standard integral push-buttons with LCD.
375 Field Communicator.
Rosemount 3490 Series Universal Control Unit.
Rosemount AMS
™
Suite
Materials of construction
Wet-side material PVDF.
Body and cover material Polyurethane-covered Aluminum.
Cover seal Silicone rubber.
Cover screws 316 Stainless Steel.
Transducer body seal EPDM.