Reference Manual
00809-0100-4840, Rev. BA
July 2008
4-21
Rosemount 3100 Series
c) If the indicated value is correct, press the red button ↵ to exit to the menu.
(The “LEUEL @ max” re-appears. To get to the next menu, press
↓.)
d) Press the blue button → to start the editing mode. The first digit flashes to
indicate it can now be edited.
e) Press the green button
↓ repeatedly to edit the flashing digit.
f) Press the blue button
→ to move to the next digit. The digit flashes to
indicate it can be edited.
g) Repeat steps (e) and (f) until the last digit is flashing, and edited as
required.
h) Press the blue button
→ to confirm the new value. (The flashing stops.)
i) If the new value is correct, press the red button
↵ to save. The display
changes to the next menu option.
j) If the new value is incorrect, press the blue button
→ to exit to the menu.
The menu option “LEUEL @ max” re-appears; re-start at step (b) or
press
↓ for the next menu option.
Maximum Flow Entry
(The 3102/3105)
Screen display Flo @ max
Factory default value 1.000
This menu option is offered if the selected duty is Flow and requires entry of
the maximum flow capability of the chosen structure (not the maximum flow
expected in the application.)
NOTE:
This menu option is in the programming menu. See Figure C-2 on page C-3
for a map of the menu structure and how to access the menu options.
To change the Flo@max value:
a) If entering the menu system from the PV display, press the green button
↓
repeatedly until the “Flo @ max” menu is indicated (see above note.)
b) Press the blue button
→ to enter the “Flo @ max” menu and display the
present Flo@max value.
c) If the Flo@max value is correct, press the red button
↵ to exit to the menu.
(The menu “Flo @ max” re-appears. To get to the next menu, press
↓.)
d) Press the blue button → to start the editing mode. The first digit flashes to
indicate it can now be edited.
e) Press the green button
↓ repeatedly to edit the flashing digit.
f) Press the blue button
→ to move to the next digit. The digit flashes to
indicate it can be edited.
g) Repeat steps (e) and (f) until the last digit is flashing, and edited as
required.
h) Press the blue button
→ to confirm the new value. (The flashing stops.)
i) If the new value is correct, press the red button
↵ to save. The display
changes to the next menu option.
j) If the new value is incorrect, press the blue button
→ to exit to the menu.
The menu option “Flo @ max” re-appears; re-start at step (b) or press
↓
for the next menu option.
NOTE:
If the data entered allows the transmitter to calculate the maximum flow, the
4 and 20 mA points are set to 4 mA at zero flow and 20 mA at maximum flow.