Reference Manual
00809-0100-4840, Rev. BA
July 2008
5-5
Rosemount 3100 Series
e) Press the blue button to move to the next digit. The digit flashes to
indicate it can be edited.
f) Repeat steps (d) and (e) until the last digit is flashing, and edited as
required.
g) Press the blue button
to confirm the fixed loop current.
h) To change the fixed current value to a new value, press the blue button
to return to the “LOOP” menu and re-start at step (b).
i) Press the green button
to return to displaying the “tESt” menu option.
j) From “tESt”, press the red button
to change to the PV display.
Alternatively, from “tESt”, press and hold both the blue
and the red
buttons together for 2 seconds to get to the Engineering “Eng” menu
(see “Engineering Menu For The 3102 and 3105” on page 5-6.