Reference Manual
00809-0100-4021, Rev GC
Section 3: HART commissioning
April 2014
HART® commissioning
Configure Thermocouple Degradation in guided setup
Enable Thermocouple Degradation in Guided Setup: Fast Keys 2-1-7-1
1. From the Home Screen, select 2 Configure.
2. Select 1 Guided Setup.
3. Select 7 Diagnostics Suite.
4. Select 1 Config TC Diagnostic.
5. Select the sensor for which Thermocouple Diagnostic will be configured. Choose from 1
Sensor 1 or 2 Sensor 2 and press ENTER.