Reference Manual
00809-0100-4021, Rev GC
Section 3: HART commissioning
April 2014
HART® commissioning
6. Select 1 Enable to enable Thermocouple Diagnostic and press ENTER.
7. Decide if you would like to change the trigger level or the sensor you are configuring. If
so, choose 1 Yes. If not, choose 2 No. Return to Main Screen.
8. IF YES: Select a trigger level for the sensor you are configuring and press ENTER.
Choose between a fixed 5K Ohms, Baseline x 2, Baseline x 3, and Baseline x 4.
9. Review the summary provided on the communicator and press OK when satisfied or
ABORT to exit.
10. Decide if you would like to reset the baseline resistance of the thermocouple you are
configuring. If so, choose 1 Yes. If not, choose 2 No. Return to Main Screen.