Section 3: HART commissioning
April 2014
HART® commissioning
6. Select the sensor for which Thermocouple Diagnostic will be configured. Choose from 1
Sensor 1 or 2 Sensor 2 and press ENTER. Select 3 Exit to exit the setup.
7. Select 1 Enable to enable Thermocouple Diagnostic and press ENTER.
8. Decide if you would like to change the trigger level or the sensor you are configuring. If
so, choose 1 Yes. If not, choose 2 No. Return to Main Screen.
9. IF YES: Select a trigger level for the sensor you are configuring and press ENTER.
Choose between a fixed 5K Ohms, Baseline x 2, Baseline x 3, and Baseline x 4.
10. Review the summary provided on the communicator and press OK when satisfied or
ABORT to exit.