108
Reference Manual
00809-0100-4021, Rev GC
Section 3: HART commissioning
April 2014
HART® commissioning
11. Decide if you would like to reset the baseline resistance of the thermocouple you are
configuring. If so, choose 1 Yes. If not, choose 2 No. Return to Main Screen.
12. IF YES: Review the summary provided on the communicator and press OK when
satisfied or ABORT to exit.
Disable Thermocouple Degradation in Manual Setup: Fast Keys 2-2-4-3-4
1. From the Home Screen, select 2 Configure.
2. Select 2 Manual Setup.
3. Select 4 Diagnostics.