110
Reference Manual
00809-0100-4021, Rev GC
Section 3: HART commissioning
April 2014
HART® commissioning
Active Thermocouple Degradation alerts
To verify that Thermocouple Degradation is enabled: Fast Keys 2-2-4
1. From the Home Screen, select 2 Configure.
2. Select 2 Manual Setup.
3. Select 4 Diagnostics.
4. Select 3 Sensor and Process Diagnostics.
5. 1 TC Diag Mode Snr 1 will show Enabled if Thermocouple Diagnostic is enabled for
Sensor 1, and Disabled if Thermocouple Diagnostic is disabled.
2 TC Diag Mode Snr 2 will show Enabled if Thermocouple Diagnostic is enabled for
Sensor 2, and Disabled if Thermocouple Diagnostic is disabled.