Reference Manual
00809-0100-4021, Rev GC
Section 2: Installation
April 2014
Installation
Figure 2-9. Transmitter Terminal Block
A. Sensor terminals (1 – 5)
B. Ground
Figure 2-10. Sensor Wiring Diagram for HART / 4–20 mA
3144P Single-sensor connections diagram
3144P dual-sensor connections diagram
(1) Transmitter must be configured for a 3-wire RTD in order to recognize an RTD with a compensation loop.
(2) Emerson Process Management provides 4-wire sensors for all single-element RTDs. Use these RTDs in 2-wire or 3-wire configurations by leaving the unneeded leads
disconnected and insulated with electrical tape.
“+”
A
Test
B
“-”
“+”
“-”
B
A
Wiring connections
Wiring connections
(with “T1” integral transient protection option)
4-wire RTD
and Ohms
T/Cs and
Millivolts
RTD with
Compensation Loop
(1)
2-wire RTD
and Ohms
3-wire RTD
and Ohms
(2)
T/Hot Backup/Dual
Sensor with
2 RTDs
T/Hot Backup/Dual
Sensor with 2
Thermocouples
T/Hot
Backup/Dual
Sensor with RTDs/
Thermocouples
(2)
T/Hot
Backup/Dual
Sensor with
RTDs/
Thermocouples
(2)
T/Hot Backup/Dual
Sensor with 2 RTDs
with Compensation
Loop
(2)