Section 3: HART commissioning
April 2014
HART® commissioning
Disable Hot Backup in guided setup: Fast Keys 2-1-5
1. From the Home Screen, choose 2 Configure.
2. Choose 1 Guided Setup.
3. Choose 5 Config Hot Backup.
4. When prompted, choose 1 Yes to disable Hot Backup. To reconfigure Hot Backup,
choose 2 No.
5. When prompted, choose which variable you would like as your primary variable (PV)
and press ENTER. With Hot Backup disabled, the PV may be Sensor 1 Temperature,
Sensor 2 Temperature, Differential Temperature, Average Temperature, or First Good
Temperature.