6.2 EASY ACCESSING DIAGRAM FOR PAGES
TECHNICIAN
PASSWORD
0000
How to access to technician pages?
There must be no selected parameter in current page.
The current page must be one of the following pages which are in user field;
PROCESS VALUES, SYSTEM MONITORING, FEEDING CONSUMPTION, WEIGHING1 LOG,
WEIGHING2 LOG, WEIGHING3 LOG, ELECTRICITY ENERGY CONSUMPTION, WATER CONSUMPTION,
SET VALUES, SET SHUTTER, FEEDING PARAMETERS, LIGHTING PARAMETERS, ALARM SET VALUES,
PROCESS OUTPUTS, MAX MIN VALUES 1, MAX MIN VALUES 2, EVENTS
Under these conditions, push button.
This page will be seen;
If right password is entered, then HEATING1 PARAMETERS page which is the first page of the
technician pages is accessed.
HEATING1 PARAMETERS
SENSOR : ROOM1
CONTROL :PROPORTION
SET POINT: RELATIVE
HYST : 1.0°C
PERIOD : 40SEC
OFFSET : 0.0°C
PROP RAMP: 50SEC
HEATING2 PARAMETERS
SENSOR : ROOM1
CONTROL :PROPORTION
SET POINT: RELATIVE
HYST : 1.0°C
PERIOD : 40SEC
OFFSET : 0.0°C
PROP RAMP: 50SEC
COOLING PARAMETERS
SENSOR : ROOM1
CONTROL :PROPORTION
SET POINT: RELATIVE
HYST : 1.0°C
PERIOD : 40SEC
OFFSET : 0.0°C
PROP RAMP: 50SEC
HUMIDITY
CONTROL :PROPORTION
HYST : 10%
PERIOD : 40SEC
OFFSET : 0%
PROP RAMP: 50SEC
VENTIL. PARAMETERS
SHIFTING : ON
SHIFT&PRP PER: 10MIN
DLY BTWN FANS: 5SEC
PRPRTN RAMP : 50SEC
SENSOR : ROOM1
FAN CONT.: TUNNEL
SET VENTILATION<°C>
VENT1: 0.5 VENT3: 2.5
VENT2: 1.0 VENT3: 3.0
VENT3: 1.5 VENT3: 3.5
VENT4: 2.0 VENT3: 4.0
SHUTTER PARAMETERS
STROKE TIME: 100SEC
STEP : 0.1%
TEMPERATURE SETTINGS
ROOM1 OFFSET: 0.0°C
ROOM2 OFFSET: 0.0°C
OUT. OFFSET : 0.0°C
HUM. OFFSET : 0%
SENS MINMAX : ROOM1&2
SENS OPENING: ROOM1&2
CONTROL FUNC PAGE 1
CURVE : DISABLE
HUMIDITY : ENABLE
OUTSIDE TEMP: ENABLE
COMMUNICATE : ENABLE
LOAD DEFAULT: NO
WATER CONSUM: ENABLE
ELECT CONSUM: ENABLE
CONTROL FUNC PAGE 2
FEEDING : ENABLE
CHICKS W1 : ENABLE
CHICKS W2 : ENABLE
CHICKS W3 : ENABLE
LIGHTING : ENABLE
LIGHT CONT: MODULATE
FEED UNIT PARAMETERS
UNIT : TIME
FEED PER MIN: 6.0KG
TARE : NO
REF WEIGHT : 250KG
TAKE REF WEIGHT: NO
FEED OFFSET : 0KG
WEIGHT1 CALIBRATION
TARE: NO
REF WEIGHT: 5000GR
TAKE REF WEIGHT: NO
5000GR
WEIGHT2 CALIBRATION
TARE: NO
REF WEIGHT: 5000GR
TAKE REF WEIGHT: NO
5000GR
WEIGHT3 CALIBRATION
TARE: NO
REF WEIGHT: 5000GR
TAKE REF WEIGHT: NO
5000GR
AVERAGE WEIGH1
INITIAL WEIGH: 100GR
MINIMUM LIMIT: 30%
MAXIMUM LIMIT: 15%
AVERAGE WEIGH2
INITIAL WEIGH: 100GR
MINIMUM LIMIT: 30%
MAXIMUM LIMIT: 15%
AVERAGE WEIGH3
INITIAL WEIGH: 100GR
MINIMUM LIMIT: 30%
MAXIMUM LIMIT: 15%
WEIGHING PARAMETERS
SS TIME : 1.0SEC
SS LIMIT VAL: 15GR
AW MIN SMPL : 100
AW SMPL PER : 2HR
WATER AND ELECTRICITY
CONSUMPTION PER PULSE
ELECTRICITY: 1000WH/P
WATER : 0.10LT/P
MODBUS
BAUD RATE : 3
STOP BIT : 0
PARITY BIT: 0
SLAVE ID : 1
EDIT PASSWORDS
TECHNICIAN: 0000
USER : 0000
ENTER CAL
PASSWORD
0000
=
=
NOTES:
1: If CONTROL FUNC PAGE 2 PAGE FEEDING
parameter is enabled then this page is visible.
2: If CONTROL FUNC PAGE 2 PAGE CHICKS W1
parameter is enabled then this page is visible.
3: If CONTROL FUNC PAGE 2 PAGE CHICKS W2
parameter is enabled then this page is visible.
4: If CONTROL FUNC PAGE 2 PAGE CHICKS W3
parameter is enabled then this page is visible.
5: If CONTROL FUNC PAGE 2 PAGE CHICKS W1
parameter is enabled or
CONTROL FUNC PAGE 2 PAGE CHICKS W2
parameter is enabled or
CONTROL FUNC PAGE 2 PAGE CHICKS W3
parameter is enabled then this page is visible.
6: If CONTROL FUNC PAGE 1 PAGE COMMUNICATE
parameter is enabled then this page is visible.
7: If CONTROL FUNC PAGE 1 PAGE ELECT CONSUM
parameter is enabled or
CONTROL FUNC PAGE 1 PAGE WATER CONSUM
parameter is enabled then this page is visible.
8: If CONTROL FUNC PAGE 1 PAGE HUMIDITY
parameter is enabled then this page is visible.
9: If VENTIL. PARAMETERS PAGE FAN CONT.
parameter is BASIC&TUN. then this page is shown.
10: If the device is EPC-4A, then CHICKS W3
parameter is not shown.
11: If the device is EPC-1A, EPC-3A, EPC-4A then
this page is shown instead of WEIGHT3 CALIBRATION.
12: If the device is EPC-4A, then this page is not shown.
(NOTE: 1) (EPC 3&4)
(NOTE: 2) (EPC 4)
(NOTE: 3) (EPC 4)(NOTE: 4) (EPC 4)(NOTE: 2) (EPC 4)
(NOTE: 3) (EPC 4)
(NOTE: 4) (EPC 4)
(NOTE: 5) (EPC 4)
(NOTE: 7) (EPC 4)
(NOTE: 6)
(NOTE: 8)
47
CONTROL FUNC PAGE 1
CURVE : DISABLE
HUMIDITY : ENABLE
OUTSIDE TEMP: ENABLE
COMMUNICATE : ENABLE
LOAD DEFAULT: NO
EPC 4 EPC 3
CONTROL FUNC PAGE 2
FEEDING : ENABLE
LIGHTING : ENABLE
LIGHT CONT: MODULATE
EPC 4 EPC 3
SHUTTER PARAMETERS
STROKE TIME: 100SEC
STEP : 0.1%
SHUT.FEEDB.: ENABLE
EPC-1A, EPC-3A, EPC-4A
SET VENTILATION<°C>
VENT1: 0.5 VENT3: 2.5
VENT2: 1.0 VENT3: 3.0
VENT3: 1.5 VENT3: 3.5
VENT4: 2.0 VENT3: 4.0
F.HYS: 0.5 C.HYS: 1.0
FAN ANALOG: BASIC
BASIC VENT:PROPORTION
(NOTE: 9)
(NOTE: 10)
SHUTTER CALIBRATION
SHUTTER CLOSE: NO
SHUTTER OPEN: NO
1000
(NOTE: 11)
(NOTE: 12)