40
Note: dis = disable
Min
Default
Unit
CANBUS ERROR SET (Engine->CanBus error set)
Max
Can Fault Actions:
0- Disable
1- Warning Non-Latching
2- Warning (Alarm Only, No Shutdown)
3- Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
4- Shutdown (Alarm And Shutdown)
0
0 2
0
0(dis) 4
CAN fault activation
CAN fault actions
SecCan Fault Delay
10
2 250
CAN fault delay
Can Fault Activation:
0- Active From Starting
1- Active From Safety On
2- Always Active
J1939 Amber Warning Lamp Actions:
0- Disable
1- Warning Non-Latching
2- Warning (Alarm Only, No Shutdown)
3- Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
4- Shutdown (Alarm And Shutdown)
2
0 2
0
0(dis) 4
Amber warn.activation
Amber warn.actions
SecJ1939 Amber Warning Lamp Delay
2
0 250
Amber warn.delay
J1939 Amber Warning Lamp Activation:
0- Active From Starting
1- Active From Safety On
2- Always Active
J1939 Red Stop Lamp Actions:
0- Disable
1- Warning Non-Latching
2- Warning (Alarm Only, No Shutdown)
3- Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
4- Shutdown (Alarm And Shutdown)
2
0 2
0
0(dis) 4
Red stop activation
Red stop actions
SecJ1939 Red Stop Lamp Delay
2
0 250
Red stop delay
J1939 Red Stop Lamp Activation:
0- Active From Starting
1- Active From Safety On
2- Always Active