41
Note: dis = disable
Min
Default
ENGINE MAINTENANCE (Engine->Maintenance)
Max
Running Hours Interval
Maintenance Date Interval
Force Engine Shutdown When Maintenance Is Due
Engine Running Hour (Lsb)
5000
Engine Running Hour
0(dis) 9999
Engine Running Hour(Msb)
ENABL/DISBL
0
0 255
DISBL
0
0
0(dis)
12 6
0 255
0 14
Maint. date interval
Eng. stop when maint
Eng. running hour(lsb)
Eng. running hour
Eng. running hour(msb)
Running hour interval
Unit
Hour
Month
Maintenance Okay
NO
Maintenance okay
YES/NO
The user can change the engine running hours value by using these parameters (Engine Running
Hour (Lsb) , Engine Running Hour and Engine Running Hour (Msb)).
For example; if the engine running hours was changed 75112 hours, the values of these
parameters was calculated as follows;
Engine Running Hour (Msb) = 75112 / 65536
= 1
Intermediate Value = 75112 – (Engine Running Hour (Msb) * 65536)
= 75112 – (1 * 65536)
= 9576.
Engine Running Hour = Intermediate Value / 256
= 9576 / 256
= 37
Engine Running Hour (Lsb) = Intermediate Value – (Engine Running Hour * 256)
= 9576 – (37 * 256)
= 104
Min
Default
LOAD TEST (Engine->Load test)
Max
Unit
1-NO LOAD
Disable/enable select
Disable, No Load or On Load Selection
0-DISABLE
1-NO LOAD
2-ON LOAD
Disable, No Load or On Load Selection
DISABLE Test mode disable.
NO LOAD The generator will be running without taking the load in test mode.
ON LOAD The generator will be running with load in test mode.
:
:
: