Commissioning with an operating menu (onsite display/FieldCare) Cerabar M, Deltabar M, Deltapilot M
134 Endress+Hauser
Expert → Diagnosis → Diagnostic list
Reset logbook (159)
Options
With this parameter, you reset all the messages of the "Last diag. code (072)"
parameter and the "Last diag. 1 (085)" to "Last diag. 10 (094)" event log.
Options:
•Abort
•Confirm
Factory setting:
Abort
Min. meas. press. (073)
Display
Displays the lowest pressure value measured (peakhold indicator). You can reset
this indicator by means of the "Reset peakhold (161)" parameter.
Max. meas. press. (074)
Display
Displays the highest pressure value measured (peakhold indicator). You can reset
this indicator by means of the "Reset peakhold (161)" parameter.
Reset peakhold (161)
Options
You can reset the "Min. meas. press." and "Max. meas. press." indicators with this
parameter.
Options:
•Abort
•Confirm
Factory setting:
Abort
Alarm behav. P (050)
Selection
Configure the current output for when the sensor limits are undershot or overshot.
Options:
•Warning
The device continues measuring. An error message is displayed. The measuring
value status shows "UNCERTAIN".
•Alarm
The measuring value status shows "BAD". An error message is displayed
Factory setting:
Warning
Operating hours (162)
Display
Displays the hours of operation. This parameter cannot be reset.
Config. counter (100)
Display
Displays the configuration counter.
This counter is increased by one every time a parameter or group is changed. The
counter counts up to 65535 and then starts again at zero.
Parameter name Description
Diagnostic 1 (075)
Diagnostic 2 (076)
Diagnostic 3 (077)
Diagnostic 4 (078)
Diagnostic 5 (079)
Diagnostic 6 (080)
Diagnostic 7 (081)
Diagnostic 8 (082)
Diagnostic 9 (083)
Diagnostic 10 (084)
These parameters contain up to ten diagnosis messages that are currently pending,
arranged in order of priority.