Commissioning with an operating menu (onsite display/FieldCare) Cerabar M, Deltabar M, Deltapilot M
136 Endress+Hauser
PV PV = Primary Value
Analog Input Block
Deltabar M
Transducer Block Sensor
Sensor trim
Position
adjustment
Simulation value
Pressure
Damping
P
Pressure Level Simulation value:
- Level
- Tank content
Flow Simulation value:
- Flow
PV PV = Primary Value
Analog Input Block
Sim. pressure (113)
Entry
Enter the simulation value.
See also "Simulation mode (112)".
Prerequisite:
•"Simulation mode (112)" = Pressure
Value when switched on:
Current pressure measured value
Sim. flow (114) (Deltabar M)
Entry
Enter the simulation value.
See also "Simulation mode (112)".
Prerequisite:
•"Measuring mode (005)" = Flow and "Simulation mode (112)" = Flow
Sim. level (115)
Entry
Enter the simulation value.
See also "Simulation mode (112)".
Prerequisite:
•"Measuring mode (005)" = Level and "Simulation mode (112)" = Level
Sim. tank cont. (116)
Entry
Enter the simulation value.
See also "Simulation mode (112)".
Prerequisites:
•"Measuring mode (005)" = Level, "Lin. mode (037)" = "Activate table" and
"Simulation mode (112)" = Tank content.
Sim. error no. (118)
Entry
Enter the diagnostic message number.
See also "Simulation mode (112)".
Prerequisite:
•"Simulation mode (112)
" = Alarm/warning
Value when switched on:
484 (simulation active)
Parameter name Description