Cerabar M, Deltabar M, Deltapilot M Commissioning with the FF configuration program
Endress+Hauser 173
Electr. serial no./
ELECTRONIC_SERIAL
_NUMBER
Display
Index: 46
Data type: visible string
Access: read only
Displays the serial number of the main electronics (11 alphanumeric characters).
Sci octet str/
SCI_OCTET_STRING
Display
Index: 47
Data type: visible string
Access: wr for Auto,
OOS
Internal service parameter.
Download select./
DOWNLOAD_OVERWR
ITE_SELECTION
Options
Index: 48
Data type: unsigned8
Access: wr for Auto,
OOS
Selection of data records for the Upload/Download function in Fieldcare.
Prerequisite:
DIP switch 1, 3, 4 and 5 set to "OFF", DIP switch 2 set to "ON" (see picture in
Chap. 6.2.1)).
A download with the factory setting "Copy configuration" causes all parameters needed
for a measurement to be downloaded. If the "Copy configuration" setting is changed, it
takes effect only when a corresponding release code is entered into the parameter
"Operator code/S_W_LOCK".
Options:
• Copy configuration: With this option, general configuration parameters are
overwritten except for serial number, order number, calibration, position
adjustment, application, and tag information.
• Device replacement: With this option, general configuration parameters are
overwritten except for serial number, order number, calibration, position
adjustment, and PD tag.
• Electronics replacement: With this option, general configuration parameters are
overwritten except for position adjustment.
The control strategy is not affected by a download.
Selection of device replacement or electronics replacement takes effect only if a
corresponding release code has been entered beforehand.
Factory setting:
Copy configuration
Code definition/
USER_S_W_UNLOCK
Entry
Index: 49
Data type: unsigned16
Access: wr for Auto,
OOS
Use this function to enter a release code with which the device can be unlocked.
User input:
• A number between 0 and 9999
Factory setting:
0
Capability level/
CAPABILITY_LEVEL
Display
Index: 50
Data type: unsigned8
Access: read only
This parameter is integrated into a device to indicate what capability level is supported
by the device.
Description: capability level supported by the device. A value of zero (0) indicates that
the device does not support multiple capability levels.
Factory setting:
1
Resource Block - Endress+Hauser parameters
Parameter Description