Description of device parameters Ceraphant PTP31B, PTP33B
54 Endress+Hauser
13.3 EF menu (extended functions)
RES Reset
Navigation EF → RES
Description
L
WARNING
Confirming the reset by selecting "YES" causes an immediate device reset to the
factory settings of the order configuration.
If the factory settings have been changed, downstream processes might be affected
following a reset (the behavior of the switch output or current output might be changed).
‣
Make sure that downstream processes are not started unintentionally.
To carry out a reset, you must answer the query with "Yes". The reset is not subject to
additional locking, such as in the form of device locking. The reset also depends on the
device status.
Any customer-specific configuration carried out at the factory is not affected by a reset
(customer-specific configuration remains).
The following parameters are not reset when a reset is performed:
• LO
• HI
• LST
• RVC
A reset to the factory settings also includes the locking code configured in the "COD"
parameter. The locking code is reset to "0000".
Value at switch-on NO
Note Must be actively changed to "YES".
The last error is not reset in a reset.
Options • NO
• YES
Factory setting NO
dS1/dS2 switching delay time, output 1/2
dR1/dR2 switchback delay time, output 1/2
Note The switch delay time/switchback delay time function is implemented using the
"dS1/dS2" and "dR1/dR2" parameters. Since the parameter settings depend on one
another, the parameters are described all together.
• dS1 = switching delay time, output 1
• dS2 = switching delay time, output 2
• dR1 = switchback delay time, output 1
• dR2 = switchback delay time, output 2
Navigation EF → dS1/dS2
EF→ dR1/dR2