Ceraphant PTP31B, PTP33B Description of device parameters
Endress+Hauser 55
Description To prevent constant switch-on and switch-off if values are around the switch point "SP1/
SP2" or the switchback point "RP1/RP2", a delay in a range of 0 – 50 seconds, to two
decimal places, can be set for the individual points.
If the measured value leaves the switching range during the delay time, the delay time
starts again from scratch.
Example SP1/SP2 = 2 bar (29 psi)
RP1/RP2 = 1 bar (14.5 psi)
dS1/dS2 = 5 seconds
dR1/dR2 = 2 seconds
dS1/dS2: ≥2 bar (29 psi) must be present for at least 5 seconds for SP1/SP2 to become
active.
dR1/dR2: ≤1 bar (14.5 psi) must be present for at least 2 seconds for RP1/RP2 to become
active.
2
1
0
SP1/SP2
RP1/RP2
dS1
dS2
dS1
dS2
dR1
dR2
0
HNO
p
t
1
HNC
A0022944
0 0-signal. Output open in quiescent state.
1 1-signal. Output closed in quiescent state.
2 Hysteresis (difference between the value of the switch point "SP1/SP2" and the value of the switchback point
"RP1/SP2")
HNO Closing
HNC NC contact
SP1/
SP2
Switch point 1/2
RP1/
RP2
Switchback point 1/2
dS1/
dS2
Set time for which the specific switch point must be reached continuously without interruption until an
electrical signal change takes place.
dR1/
dR2
Set time for which the specific switchback point must be reached continuously without interruption until an
electrical signal change takes place.
Value at switch-on 0
Input range 0.00 - 50.00 seconds
Factory setting 0
HNO NO contact for hysteresis function