Ceraphant PTP31B, PTP33B Technical data
Endress+Hauser 75
15.4 Environment
15.4.1 Ambient temperature range
Device Ambient temperature range
1)
PTP31B
PTP33B
–20 to +70 °C (–4 to +158 °F)
1) Exception: the following cable is designed for an operating temperature range of
–25 to +70 °C (–13 to +158 °F): Product Configurator order code for "Accessory enclosed", option "RZ".
15.4.2 Storage temperature range
–40 to +85 °C (–40 to +185 °F)
15.4.3 Climate class
Device Climate class Note
PTP31B
PTP33B
Class 3K5 Air temperature: –5 to +45 °C (+23 to +113 °F),
relative humidity: 4 to 95 %
satisfied according to IEC 721-3-3 (condensation not possible)
15.4.4 Degree of protection
Device Connection Climate class Option
1)
PTP31B
PTP33B
Cable5 m (16 ft) IP66/67 NEMA type 4X enclosure D
PTP31B
PTP33B
Cable10 m (33 ft) IP66/67 NEMA type 4X enclosure E
PTP31B
PTP33B
Cable25 m (82 ft) IP66/67 NEMA type 4X enclosure F
PTP31B
PTP33B
M12 plug made of plastic IP65/67 NEMA type 4X enclosure M
PTP31B
PTP33B
Valve plug ISO4400 M16 IP65 NEMA type 4X enclosure U
PTP31B
PTP33B
Valve plug ISO4400 NPT ½ IP65 NEMA type 4X enclosure V
1) Product Configurator, order code for "Electrical connection"
15.4.5 Vibration resistance
Test standard Vibration resistance
IEC 60068-2-64:2008 Guaranteed for 5 to 2000Hz: 0.05g
2
/Hz
15.4.6 Electromagnetic compatibility
• Interference emission as per EN 61326-1 equipment B
• Interference immunity as per EN 61326-1 (industrial sector)
• NAMUR recommendation EMC (NE21)
• Maximum deviation: 1.5% for TD 1:1
For further details refer to the Declaration of Conformity.