Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (Local operation and FieldCare)
Endress+Hauser 145
CUST. UNIT FACT. P (317)
Entry
Enter the conversion factor for a customer-specific pressure unit.
The conversion factor must be entered in relation to the SI unit "Pa". See also
CUSTOMER UNIT P.
Prerequisite:
PRESS. ENG. UNIT = User unit
Example:
You want the measured value to be displayed in "PU" (PU: packing unit).
MEASURED VALUE =10000 Pa i 1 PU
Entry CUSTOMER UNIT P: PU
Entry CUST. UNIT FACT. P: 0.0001
Result: MEASURED VALUE = 1 PU
Factory setting:
1.0
DAMPING VALUE (247)
Entry
Enter damping time (time constant τ).
The damping affects the speed at which all subsequent elements, such as the local
operation, measured value and OUT value of the Analog Input Block react to a change in
the pressure.
Input range:
0.0 to 999.0 s
Factory setting:
2.0 s or as per order specifications
Table 7: OPERATING MENU SETTINGS BASIC SETUP "Pressure"