Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (Local operation and FieldCare)
Endress+Hauser 153
EMPTY CALIB. (010)
Entry
Enter the level, volume, mass or percentage value for the lower calibration point (empty
container).
The container is either empty or part full. The measured pressure is converted to a height
value using the HEIGHT UNIT, DENSITY UNIT and ADJUST DENSITY parameters and
displayed. By means of the parameter EMPTY CALIB., you assign a level, volume, mass or
percentage value to the height value. The unit is selected via the OUTPUT UNIT
parameter (→ ä 152).
Prerequisite:
• CALIBRATION MODE = Wet
!
Note!
For this parameter, the local operation shows the level value to be entered and the
pressure present at the device. In order for the level value to be saved together with the
pressure present at the device, the entry field for the level value must first be activated
using the "+"- or "–" key before confirming with the "E" key. This applies also if the level
value is to remain unchanged.
Factory setting:
0.0
FULL CALIB. (004)
Entry
Enter the level, volume, mass or percentage value for the upper calibration point (full
container).
The container is either completely or almost full. The measured pressure is converted to a
height value using the HEIGHT UNIT, DENSITY UNIT and ADJUST DENSITY
parameters and displayed. By means of the parameter FULL CALIB., you assign a level,
volume, mass or percentage value to the height value. The unit is selected via the
OUTPUT UNIT parameter (→ ä 152).
Prerequisite:
• CALIBRATION MODE = Wet
!
Note!
For this parameter, the local operation shows the level value to be entered and the
pressure present at the device. In order for the level value to be saved together with the
pressure present at the device, the entry field for the level value must first be activated
using the "+"- or "–" key before confirming with the "E" key. This applies also if the level
value is to remain unchanged.
Factory setting:
100.0
EMPTY CALIB. (010)
Entry
Enter the level, volume, mass or percentage value for the lower calibration point (empty
container).
The values entered for the EMPTY CALIB. and EMPTY HEIGHT parameters form the
height-level value pair for the lower calibration point. The unit is selected via the
OUTPUT UNIT parameter (→ ä 152).
Prerequisite:
• CALIBRATION MODE = Dry
Factory setting:
0.0
EMPTY HEIGHT (009)
Entry
Enter the height value for the lower calibration point (container empty). The unit is
selected via the HEIGHT UNIT parameter (→ ä 152).
→ See also EMPTY CALIB.
Prerequisite:
• CALIBRATION MODE = Dry
Factory setting:
0.0
FULL CALIB. (004)
Entry
Enter the level, volume, mass or percentage value for the upper calibration point (full
container).
The values entered for the FULL CALIB. and FULL HEIGHT parameters form the height-
level value pair for the upper calibration point. The unit is selected via the OUTPUT UNIT
parameter (→ ä 152).
Prerequisite:
• CALIBRATION MODE = Dry
Factory setting:
100.0
Table 9: OPERATING MENU → SETTINGS → BASIC SETUP "Level",
LEVEL SELECTION "Level easy height"
Parameter name Description