Parameter description (Local operation and FieldCare) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
184 Endress+Hauser
TEMP. ENG. UNIT (318)
Selection
Select the unit for the temperature measured values.
→ See also PCB TEMPERATURE (→ ä 197) and SENSOR TEMP. (→ ä 201).
Options:
•°C
•°F
•K
•R
Factory setting:
°C
DENSITY UNIT (001)/(812)
Selection
Select the density unit.
Options:
•g/cm
3
•kg/dm
3
•kg/m
3
• US lb/in
3
• US lb/ft
3
Factory setting:
kg/dm
3
ADJUST DENSITY
(007)/(316)
Entry
Enter the density of the fluid.
!
Note!
LIN. MEASURAND: "% (Level)", "Mass" and "Volume" and COMB. MEASURAND:
If you change to dry calibration after a wet calibration using the CALIBRATION MODE
parameter (→ ä 161 or → ä 174), the density for the ADJUST DENSITY and PROCESS
DENSITY parameters must be entered correctly before changing the calibration mode. If
the pressure falls with increasing levels (LIN. MEASURED: volume), such as in the case of
a residual volume measurement, a negative value must be entered for this parameter.
Factory setting:
1.0
PROCESS DENSITY
(025)/(811)
Entry
Enter a new density value for density correction.
The calibration was carried out with the medium water, for example. Now the container
is to be used for another fluid with another density. The calibration is corrected
appropriately by entering the new density value in the PROCESS DENSITY parameter.
!
Note!
LIN. MEASURAND: "% (Level)", "Mass" and "Volume" and COMB. MEASURAND:
If you change to dry calibration after a wet calibration using the CALIBRATION MODE
parameter (→ ä 161 or → ä 174), the density for the ADJUST DENSITY and PROCESS
DENSITY parameters must be entered correctly before changing the calibration mode. If
the pressure falls with increasing levels (LIN. MEASURED: volume), such as in the case of
a residual volume measurement, a negative value must be entered for this parameter.
Factory setting:
1.0
Table 16: OPERATING MENU → SETTINGS → EXTENDED SETUP "Level"
Parameter name Description