Troubleshooting Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
216 Endress+Hauser
740 (E740) Error
C
C>Calculation overflow,
bad configuration
20 5 Level measuring mode: the
measured pressure has
undershot the value for Scale
In/SCALE_IN, EU at 0%/EU_0,
HYDR. PRESS. MIN. or
overshot the value for Scale In/
SCALE_IN, EU at 100%/
EU_100, HYDR. PRESS MAX.
Check configuration and carry
out calibration again if
necessary.
Select a device with a suitable
measuring range.
28
Flow measuring mode: the
measured pressure has
undershot the value for Scale
In/SCALE_IN, EU at 100%/
EU_100, Max Press. Flow/
MAX_PRESS_FLOW
Check configuration and carry
out calibration again if
necessary.
Select a device with a suitable
measuring range.
741 (A741) Alarm
B
B>Tank Height
(TANK_HEIGHT) out of
edit limits
18 7 Level Min/LEVEL_MIN or
Level Max/LEVEL_MAX has
been changed.
Perform reset (code 2710) and
recalibrate the device.
44
742 (A742) Alarm
B
B>Sensor connection
error (upload)
20 5 Electromagnetic effects are
greater than specifications in the
technical data.
See Technical Information
TI00382P (Deltabar S),
TI00383P (Cerabar S) or
TI00416P (Deltapilot S). This
message normally only appears
briefly.
Wait a few minutes.
Perform reset (code 7864) and
recalibrate the device.
19
Cable connection sensor –main
electronics disconnected.
Check cable connection and
repair if necessary.
Sensor defect. Replace sensor.
743 (E743) Alarm
B
B>Electronic PCB error
during initialization
20 5 Electromagnetic effects are
greater than specifications in the
technical data.
See Technical Information
TI00382P (Deltabar S),
TI00383P (Cerabar S) or
TI00416P (Deltapilot S). This
message normally only appears
briefly.
Wait a few minutes.
Restart the device. Perform reset
(Code 62).
15
Main electronics defect. Replace main electronics.
744 (A744) Alarm
B
B>Main electronic PCB
error
20 5 Electromagnetic effects are
greater than specifications in the
technical data.
See Technical Information
TI00382P (Deltabar S),
TI00383P (Cerabar S) or
TI00416P (Deltapilot S).
Restart the device. Perform reset
(Code 62).
Block off electromagnetic effects
or eliminate source of
disturbance.
12
Main electronics defect. Replace main electronics.
745 (W745) Warning
C
C>Sensor data unknown 17 0 Sensor does not suit the device
(electronic sensor nameplate).
Device continues measuring.
Replace sensor with a suitable
sensor.
55
Code Error
type/
NA 64
Message/description XD_
ERROR
Value
BLOCK_
ERROR
Bit
Cause Measure Prio-
rity

Table of Contents