Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Troubleshooting
Endress+Hauser 215
727 (E727) Error
C
C>Sensor pressure error
- overrange
20 5 Electromagnetic effects are
greater than specifications in the
technical data.
See Technical Information
TI00382P (Deltabar S),
TI00383P (Cerabar S) or
TI00416P (Deltapilot S).
Block off electromagnetic effects
or eliminate source of
disturbance.
29
Pressure is outside permitted
range.
Check pressure present, reduce
or increase if necessary.
Sensor defect. If the pressure is within the
permitted range, replace sensor.
728 (A728) Alarm
B
B>RAM error 20 9 Fault in the main electronics. Briefly disconnect device from
the power supply.
2
Main electronics defect. Replace main electronics.
729 (A729) Alarm
B
B>RAM error 20 9 Fault in the main electronics. Briefly disconnect device from
the power supply.
3
Main electronics defect. Replace main electronics.
730 (E730) Error
C
C>Pminalarm Window
(PMIN_ALARM_
WINDOW) undershot
19 7 Pressure measured value has
undershot the value specified for
the Pminalarm Window/
PMIN_ALARM_WINDOW
parameter.
Check system/pressure
measured value.
Change value for Pminalarm
Window/PMIN_ALARM_
WINDOW if necessary.
( ä 92 and ä 208)
47
731 (E731) Error
C
C>Pmaxalarm Window
(PMAX_ALARM_
WINDOW) overshot
19 7 Pressure measured value has
overshot the value specified for
the Pmaxalarm Window/
PMAX_ALARM_WINDOW
parameter.
Check system/pressure
measured value.
Change value for Pmaxalarm
Window/PMAX_ALARM_
WINDOW if necessary.
( ä 92 and ä 208.)
46
732 (E732) Error
C
C>Tminalarm Window
(TMAX_ALARM_
WINDOW) undershot
19 7 Temperature measured value
has undershot the value
specified for the Tminalarm
Window/TMAX_ALARM_
WINDOW parameter.
Check system/temperature
measured value.
Change value for Tminalarm
Window/TMAX_ALARM_
WINDOW if necessary.
( ä 92 and ä 209.)
49
733 (E733) Error
C
C>Tmaxalarm Window
(TMIN_ALARM_
WINDOW) overshot
19 7 Temperature measured value
has overshot the value specified
for the Tmaxalarm Window/
TMIN_ALARM_WINDOW
parameter.
Check system/temperature
measured value.
Change value for Tmaxalarm
Window/TMIN_ALARM_
WINDOW if necessary.
( ä 92 and ä 209.)
48
736 (A736) Alarm
B
B>RAM error 20 9 Fault in the main electronics. Briefly disconnect device from
the power supply.
4
Main electronics defect. Replace main electronics.
737 (A737) Alarm
B
B>Measurement error 20 5 Fault in the main electronics. Briefly disconnect device from
the power supply.
21
Main electronics defect. Replace main electronics.
738 (A738) Alarm
B
B>Measurement error 20 5 Fault in the main electronics. Briefly disconnect device from
the power supply.
20
Main electronics defect. Replace main electronics.
739 (A739) Alarm
B
B>Measurement error 20 5 Fault in the main electronics. Briefly disconnect device from
the power supply.
24
Main electronics defect. Replace main electronics.
Code Error
type/
NA 64
Message/description XD_
ERROR
Value
BLOCK_
ERROR
Bit
Cause Measure Prio-
rity