Gammapilot M FMG60 PROFIBUS PA Installation
Endress+Hauser 15
A0018076
A Vertical beam (90°)
B Diagonal beam (30°)
C Measurement section
1 Sample point
• To increase the accuracy of density measurements, the use of a collimator is
recommended. The collimator screens the detector against environmental radiation.
• When planning, the total weight of the measuring system must be taken into
consideration.
• The Gammapilot M should be given additional support to secure it against falling or to
prevent damage to the connecting cable.
• A clamping device (FHG61) and a measurement section (FHG62) are available as
accessories (Operating Instructions -> "Accessories" section)
3.3 Water cooling
See the Operating Instructions
BA00236F/00/EN
3.4 Post-installation check
After installing the measuring device, carry out the following checks:
• Is the device damaged (visual inspection)?
• Does the device match the measuring point specifications (ambient temperature, measuring
range etc.)?
• If available: are the measuring point number and labeling correct (visual inspection)?
• Is the measuring device sufficiently protected against sunlight?
• Are the cable glands tightened correctly?