EasyManua.ls Logo

Endress+Hauser Gammapilot M FMG60 - Post-installation check

Endress+Hauser Gammapilot M FMG60
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Gammapilot M FMG60 PROFIBUS PA Wiring
Endress+Hauser 21
4.5 Supply voltage
All of the following voltages are terminal voltages directly at the device:
Version Minimum terminal voltage Maximum terminal voltage
Standard 9 V 32 V
Ex ia (FISCO model) 9 V 17.5 V
Ex ia (Entity concept) 9 V 24 V
The current consumption is approx. 11 mA. over the entire voltage range.
4.6 Potential equalization
Before wiring, connect the potential matching line to the external ground terminal of the
transmitter. If a water cooling jacket is provided, it must be connected separately to the
potential matching line.
*
A0018086
 3 Ground terminal for connecting the potential matching line
L
CAUTION
In Ex applications, the device may only be grounded on the sensor side
Please refer to the separate documentation on applications in hazardous areas for further
safety instructions.
For optimum electromagnetic compatibility, the potential matching line should be as
short as possible and at least 2.5 mm
2
(14 AWG) in cross-section.

Other manuals for Endress+Hauser Gammapilot M FMG60

Related product manuals