Gammapilot M FMG60 PROFIBUS PA Wiring
Endress+Hauser 17
For cascade, 20 m (66 ft) per device
For Pt-100 2 m (6.6 ft). Temperature measurement should be performed as close as
possible to density measurement.
4.2 Cable entries
The number and type of cable entries depend on the device version ordered. The following are
possible:
Coupling M20x1.5. sealing range 7 to 10.5 mm (0.28 to 0.41 in)
Cable entry M20x1.5
Cable entry G1/2
Cable entry NPT1/2
M12 connector (see "Fieldbus connectors")
7/8" connector (see "Fieldbus connectors")
In addition, the Gammapilot M also has a socket to connect the separate display and operating
unit FHX40. The housing of the Gammapilot M does not have to be opened to connect the
FHX40.
1 2
3
A0018083
1 Cable entry for connection compartment 2
2 Socket for FHX40
3 Cable entry for connection compartment 1
Cable entries
A maximum of one cable gland is provided for each of the connection compartments
upon delivery. If additional cable glands are required (e.g. for cascade mode), they
must be supplied by the user.
Connecting cables should be routed away from the housing from below to prevent
moisture from penetrating the connection compartment. Otherwise, a drip loop should
be provided or the Gammapilot M should be fitted with a weather protection cover.