Commissioning Gammapilot M FMG60 PROFIBUS PA
32 Endress+Hauser
The measured value screen then appears.
The basic setup can now be performed. Press to switch to the group selection:
Press again to enter the first function of the "Basic setup" function group
6.4 Basic setup
6.4.1 "Present date" (*01)
Local display
Present date *01
17.11.04 _____10:30
DD.MM.YY ____ HH:MM
This function is used to enter the date and time of the basic setup. Each of these values must
be confirmed by pressing after entering the value.
6.4.2 "Beam type" (*02)
Local display
Beam type *02
✓ Standard/cont.
Modulated
This function is used to specify whether the radiation source used emits radiation
continuously or whether it is modulated (for gamma radiography suppression).
• Standard/continuous (permanent, continuous radiation)
• Modulated (modulated radiation source)
6.4.3 "Isotope" (*03)
Local display
Isotope *03
✓ 137 Cs
60 Co
No compens.
This function is used to specify which isotope is used for the measurement. The Gammapilot
M needs this information for decay compensation.