Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Endress+Hauser 101
Mapping in the tank bottom area
Irrespective of the definded mapping range, no mapping is recorded near the end of the
measuring range (defined in Expert → Sensor → Level → Tank/silo height). The range
for which this is the case, is defined in the Map gap parameter. In this gap the map
assumes a constant value as defined by the End of mapping and End mapping amplitude
parameters:
"End of mapping" = "Last map value"
With this setting the last value of the map remains valid within the Map gap.
2 =
1 =
A [dB]
t
3
4
A0020647
1 Envelope curve
2 Map
3 Tank/silo height
4 Map gap
"End of mapping" = "Adjustable"
With this setting the value of the mapping curve within the Map gap is defined in the End
mapping amplitude paramter.
2 =
1 =
A [dB]
t
3
4
5
A0020648
1 Envelope curve
2 Map
3 Tank/silo height
4 Map gap
5 End mapping amplitude