The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
104 Endress+Hauser
Description of parameters
Confirm distance (1045)
Navigation Expert → Sensor → Mapping → Confirm distance
Write access Maintenance
Description Confirmation whether the measured distance matches the actual distance. Depending on
the selection the device automatically determines the range over which the mapping will
be recorded.
Options • Manual map
To be selected if the range of mapping is to be defined manually in the Mapping end
point parameter. In this case it is not necessary to confirm the distance.
• Distance ok
To be selected if the measured distance matches the actual distance. The device
performs a mapping and quits the sequence ("End of sequence" appears on the display).
• Distance unknown
To be selected if the actual distance is unknown. A mapping can not be performed and
the device quits the sequence ("End of sequence" appears on the display).
• Distance too small
To be selected if the measured distance is smaller than the actual distance. The device
searches the next echo and returns to the Confirm distance parameter. The new
distance is displayed. The comparison must be repeated until the displayed distance
matches the actual distance. If this is the case, the recording of the map can be started
by selecting Distance ok.
• Distance too big
1)
To be selected if the measured distance is bigger than the actual distance. The device
adjusts the signal evaluation and returns to the Confirm distance parameter. The
distance is recalculated and displayed. The comparison must be repeated until the
displayed distance matches the actual distance.
• Tank empty
To be selected if the tank is completely empty. The device records a mapping covering
the complete length of the probe and quits the sequence ("End of sequence" appears on
the display).
• Factory map
To be selected if the present mapping curve (if one exists) is to be deleted and the
factory map is to be used instead. The device returns to the Confirm distance parameter
and a new mapping can be recorded.
1) Only available for "Expert → Sensor → Echo tracking → Evaluation mode" = "Short time history" or "Long time history".
Factory setting Distance unknown
Additional information On the local display the measured distance is displayed together with this parameter.
If the teaching procedure Distance too small or Distance too big is quit before the
distance has been confirmed, a map is not recorded and the teaching procedure is
reset after 60 s.
Distance (1124)