The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
118 Endress+Hauser
Additional information The switching behavior depends on the relative position of the two switch points.
Switch-on point > Switch-off point:
The output is closed if the measured value exceeds the switch-on point.
The output is opened if the measured value falls below the switch-off point.
t
t
A
B
C
D
A0015585
A Switch-on point
B Switch-off point
C Output closed
D Output opened
Switch-on point < Switch-off point:
The output is closed if the measured value falls below the switch-on point.
The output is opened if the measured value exceeds the switch-off point.
t
t
B
A
C
D
A0015586
A Switch-on point
B Switch-off point
C Output closed
D Output opened
Assign status (0485)
Navigation Expert → Output → Switch output → Assign status