Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Endress+Hauser 119
Prerequisite Only visible for Switch output function = Digital output.
Description Allocates a DI block or the DI output of the advanced diagnostics to the switch output.
Options Off
No digital block is allocated.
Digital output AD 1
Digital output AD 2
Digital output 1
Digital output 2
Digital output 3
Digital output 4
Factory setting Off
Switch-on delay (0467)
Navigation Expert → Output → Switch output → Switch-on delay
Prerequisite Only visible for Switch output function = Limit and Assign limitOff.
Description Defines the delay for the switching on of the output.
Range of values 0 to 100 s
Factory setting 0 s
Switch-off delay (0465)
Navigation Expert → Output → Switch output → Switch-off delay
Prerequisite Only visible for Switch output function = Limit and Assign limitOff.
Description Defines the delay for the switching off of the output.
Range of values 0 to 100 s
Factory setting 0 s
Switch output failure mode (0486)
Navigation Expert → Output → Switch output → Switch output failure mode
Description Defines the switching state of the output in the case of an error.