Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Endress+Hauser 59
Prerequisite Only visible if a linearization has been selected (i.e. Linearization typeNone)
Description Defines the unit of the linearized value.
Options Free text
t
lb
ton
kg
impGal
UsGal
cf
cm
3
dm
3
m
3
hl
l
%
Factory setting %
Additional information The selected unit is only used to be indicated on the display. The measured value is not
transformed according to the selected unit.
It is also possible to parametrize a distance-to-distance linearization, i.e. a
transformation from the level unit to a different distance unit. To do so, select the
Table linearization mode. In order to define the new level unit, select the Free text
option in the Unit after linearization parameter and enter the unit into the Free text
parameter.
Free text (2341)
Navigation Expert → Sensor → Linearization → Free text
Write access Maintenance
Prerequisite Only visible for Unit linearized = Free text.
Description Definiton of the unit
Input range Up to 32 alphanumerical characters (letters, numbers, special characters)
Factory setting Free text
Level linearized (2318) (→  53)
Prerequisite Only visible for operation via operating tool (e.g. FieldCare), not on the local display
module.