Device Functions Proline Promag 55 FOUNDATION Fieldbus 6 Block TOTALIZER
Endress+Hauser 39
6.2 Group HANDLING TOTALIZER
TOTALIZER D TOTALIZER 1 DAA
TOTALIZER 2 DAB
TOTALIZER 3 DAC
HANDLING TOTALIZER DJA Handling totalizer functions
Function description
TOTALIZER HANDLING TOTALIZER Handling totalizer functions
RESET ALL TOTALIZERS
(3800)
Use this function to reset the totals (including all overflows) of the Totalizers (1 to 3) to
zero (= RESET).
Options:
NO
YES
Factory setting:
NO
FAILSAFE ALL TOT
(3801)
Use this function to define the common response of all Totalizers (1 to 3) in case of error.
Options:
STOP
The totalizer is paused until the fault is rectified.
ACTUAL VALUE
The totalizers continue to count based on the actual flow measured value. The fault is
ignored .
HOLD VALUE
The totalizers continue to count the flow based on the last valid flow value (before the
fault occurred).
Factory setting:
STOP