Device Functions Proline Promag 55 FOUNDATION Fieldbus 7 Block BASIC FUNCTION
Endress+Hauser 41
7.1 Group FOUNDATION FIELDBUS
7.1.1 Function group CONFIGURATION
BASIC FUNCTION G FOUNDATION FIELDBUS GGA CONFIGURATION 620
Function description
BASIC FUNCTION
FOUNDATION FIELDBUS CONFIGURATION
WRITE PROTECT
(6200)
Use this function to check whether the measuring device can be write-accessed via the
fieldbus.
User interface:
OFF
Write access via FOUNDATION Fieldbus possible
ON
Write access via FOUNDATION Fieldbus not possible
Factory setting:
OFF
! Note!
Hardware write protection is activated and deactivated by means of a jumper on the I/O
board (
see Operating Instructions for Proline Promag 55 FOUNDATION Fieldbus).
SIMULATION
(6201)
Use this function to check whether a simulation in the Analog Input or Discrete Output
function block is possible.
User interface:
OFF
Simulation in the Analog Input and Discrete Output function block is not
possible.
ON
Simulation in the Analog Input and Discrete Output function block is possible
Factory setting:
ON
! Note!
The simulation mode is enabled and disabled by means of a jumper on the I/O board
(
see also Operating Instructions for Proline Promag 55 FOUNDATION Fieldbus).
The status of the simulation mode is also shown in the parameter BLOCK_ERR of the
Resource Block.
DEVICE PD-TAG
(6203)
Use this function to enter a tag name for the measuring device.
User input:
Max. 32-character text, permissible: A-Z, 0-9, +,–, punctuation marks
Factory setting:
E+H_PROMAG_55_XXXXXXXXXXX