7 Block BASIC FUNCTION Device Functions Proline Promag 55 FOUNDATION Fieldbus
48 Endress+Hauser
7.2.3 Function group ADJUSTMENT
BASIC FUNCTION G FOUNDATION FIELDBUS GGA
PROCESS PARAMETER GIA CONFIGURATION 640
EPD PARAMETER 642
ADJUSTMENT 648
Function description
BASIC FUNCTION PROCESS PARAMETER ADJUSTMENT
EPD ADJUSTMENT
(6481)
Use this function to activate the EPD adjustment for an empty or full measuring tube.
! Note!
A detailed description of the empty pipe detection function can be found on Page 46.
Options:
OFF
FULL PIPE ADJUST
EMPTY PIPE ADJUST
Factory setting:
OFF
Procedure for EPD empty pipe / full pipe adjustment
1. Empty the piping. In case of an EPD adjustment, the wall of the measuring tube
should be wetted with fluid.
2. Start empty pipe adjustment: Select "EMPTY PIPE ADJUST" and press F to confirm.
3. After empty pipe adjustment, fill the piping with fluid.
4. Start full pipe adjustment: Select "FULL PIPE ADJUST" and press F to confirm.
5. Having completed the adjustment, select the setting "OFF" and exit the function by
pressing F .
6. Now select the EMPTY PIPE DET. function (see Page 46). Switch on the empty pipe
detection by selecting ON STANDARD and press F to confirm.
" Caution!
The adjustment coefficients must be valid before you can activate the EPD function. If
adjustment is incorrect the following messages might appear on the display:
–FULL = EMPTY
The adjustment values for empty pipe and full pipe are identical. In such instances,
empty pipe adjustment/full pipe adjustment must be carried out again.
ADJUSTMENT NOT OK
Adjustment is not possible because the fluid’s conductivity is out of range.