8 Block SUPERVISION Device Functions Proline Promag 55 FOUNDATION Fieldbus
54 Endress+Hauser
8.1 Group SYSTEM
8.1.1 Function group CONFIGURATION
SUPERVISION J SYSTEM JAA CONFIGURATION 800
Function description
SUPERVISION SYSTEM CONFIGURATION
ALARM DELAY
(8005)
Use this function to define a time span in which the criteria for a fault have to be satisfied
without interruption before a fault or notice message is generated.
Depending on the setting and the type of fault, this suppression acts on:
•Display
Output blocks (AI Blocks) FOUNDATION Fieldbus interface
User input:
0 to 100 s (in steps of one second)
Factory setting:
0 s
" Caution!
If this function is activated, fault and notice messages are delayed by the time
corresponding to the setting before being transmitted to the higher-order controller
(process controller, etc.). It is therefore imperative to check in advance in order to make
sure whether a delay of this nature could affect the safety requirements of the process. If
fault and notice messages may not be suppressed, a value of 0 seconds must be entered
here.
PERMANENT STORAGE
(8007)
This function displays whether permanent saving of all parameters in the EEPROM is
switched on or off.
User interface:
OFF
ON
Factory setting:
ON