EasyManua.ls Logo

Endress+Hauser Proline Promag 55 - Selecting the GSD file in the measuring device

Endress+Hauser Proline Promag 55
130 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 Transducer Block Device functions Proline Promag 55 FOUNDATION Fieldbus
94 Endress+Hauser
3.5 Parameters of the "Display" Transducer Block
The following table shows all the Endress+Hauser-specific parameters of the "Display" Transducer
Block. These can only be changed after entering an enabling code in the "Access - Code"
parameter.
!
Note!
FOUNDATION Fieldbus parameters are described in the "FOUNDATION Fieldbus Overview"
Operating Instructions (BA013S) (available at: www.endress.com Download).
"Display" Transducer Block/base index 1800:
Parameter
Write access with
operating mode
(MODE_BLK)
Description
Access - Code AUTO - OOS All data of the measuring system are protected against inadvertent change.
Only when the code has been entered in this parameter can the
manufacturer-specific parameters be programmed and the device
configuration modified.
You can enable programming by entering:
Code 55 (factory setting)
•Private code (Page 95)
User input:
Max. 4-digit number (0 to 9999)
! Note!
If the write protection is enabled then access to the manufacturer-
specific parameters is blocked even if the right code is entered. Write
protection can be activated and deactivated by means of jumpers on the
I/O board (see Operating Instructions for Proline Promag 55
FOUNDATION Fieldbus).
You can disable programming again by entering any number (other than
the access code) in this parameter.
The Endress+Hauser service organization can be of assistance if you
lose your private code.
Certain parameters are not accessible unless a special service code is
entered. This service code is known only to the Endress+Hauser service
organization. Please contact your Endress+Hauser service center if you
require clarification.
The entry made here does not affect the local display. Thus,
programming via the function matrix must be enabled separately.
Access - Status read only Use this parameter to display the current status of the possibilities for
accessing the manufacturer-specific parameters of the device.
User interface:
LOCKED (parameterization disabled)
ACCESS CUSTOMER (parameterization enabled)
ACCESS SERVICE (parameterization enabled, access to service level)
Access - Code
Counter
read only Displays how often the customer code, service code or the digit "0"
(code free) has been entered to gain access to the function matrix.
User interface:
Max. 7-digit number: 0 to 9999999
Factory setting:
0

Table of Contents

Other manuals for Endress+Hauser Proline Promag 55

Related product manuals