Proline Promass E 100
Endress+Hauser 11
Current output 4 to 20 mA
4 to 20 mA
Failure mode Choose from:
4 to 20 mA in accordance with NAMUR recommendation NE 43
4 to 20 mA in accordance with US
Min. value: 3.59 mA
Max. value: 22.5 mA
Freely definable value between: 3.59 to 22.5 mA
Actual value
Last valid value
Pulse/frequency/switch output
Pulse output
Failure mode Choose from:
Actual value
No pulses
Frequency output
Failure mode Choose from:
Actual value
0 Hz
Defined value: 0 to 12 500 Hz
Switch output
Failure mode Choose from:
Current status
Open
Closed
PROFIBUS DP
Status and alarm
messages
Diagnostics in accordance with PROFIBUS PA Profile 3.02
Modbus RS485
Failure mode Choose from:
NaN value instead of current value
Last valid value
EtherNet/IP
Device diagnostics Device condition can be read out in Input Assembly
PROFINET
Device diagnostics According to "Application Layer protocol for decentralized periphery", Version 2.3