Promass 40 4 Wiring
Endress+Hauser 21
4.4 Post connection check
Perform the following checks after completing electrical installation of the measuring
device:
Device condition and specifications Notes
Are cables or the device damaged (visual inspection)?
Electrical connection Notes
Does the supply voltage match the specifications on the nameplate? 85...260 V AC (45...65 Hz)
20...55 V AC (45...65 Hz)
16...62 V DC
Do the cables have adequate strain relief?
Cables correctly segregated by type?
Without loops and crossovers?
Are the power supply and signal cables correctly connected? See the wiring diagram
inside the cover of the
terminal compartment
Are all screw terminals firmly tightened?
Are all cable entries installed, firmly tightened and correctly sealed?
Cables looped as water traps?
seePage20
Are all housing covers installed and firmly tightened?