Installation Solicap M FTI55, FTI56
26 Endress+Hauser
Installation in the event of buildup
Installation in plastic tanks
If buildup on the probe rod can be expected
when operating the measuring system, the
active buildup compensation function prevents
the measurement result from becoming
distorted. No cleaning work has to be
performed on the probe rod.
BA300Fxx020
When installing in a silo made of plastic, a
counter electrode must be mounted on the silo
exterior at the same height as the tensioning
weight.
The length of the edge of the counter electrode
should be approximately the same length as the
distance between the tensioning weight and
the silo wall.
TI418Fen16
In a silo with plastic walls
Ground connection
Electrical
HF field
Surface area
e.g. 1
Counter electrode
e.g.
sheet metal plate
Weight
Distance
e.g. 1 m