EasyManua.ls Logo

Endress+Hauser Solicap M FTI56 - Human Interface and Display Elements for FEI58

Endress+Hauser Solicap M FTI56
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation Solicap M FTI55, FTI56
52 Endress+Hauser
5.3 Human interface and display elements for FEI58
BA299Fen016
Green LED 1 ( ready for operation), red LED 2 ( error indicated), yellow LED 3 (switching state)
FEI58
NAMUR
-
IEC 60947-5-6
+
MIN
>2,2mA
MAX
C
1
2
GD E F
3
C
A B
LED
on
flashing
off
DIP switches (C, D, E, F) Function
D
The probe is covered during calibration.
D
The probe is uncovered during calibration.
E
Switch point adjustment: 10 pF
E
Switch point adjustment: 2 pF
F
Switching delay: 5 s
F
Switching delay: 1 s
G
Failsafe mode: MIN
The output switches safety-oriented when the probe is uncovered (signal on
alarm). For use for dry running protection and pump protection for example
G
Failsafe mode: MAX
The output switches safety-oriented when the probe is covered (signal on
alarm). For use with overfill protection for example
Key Function
A B C
X Display diagnostic code
X Display calibration situation
X X Perform calibration (during operation)
X X Delete calibration points (during startup)
X Test key , (disconnects the transmitter from the switching unit)
C
C
MAXMIN
MAX

Table of Contents

Related product manuals