Solicap M FTI55, FTI56 Commissioning
Endress+Hauser 71
Output signal FEI57S
TI418Fen54
* See ä 78 ff., "Troubleshooting"
6.4 Commissioning with the electronic insert FEI58
This chapter describes the process for commissioning the device with electronic insert FEI58.
!
Note!
The measuring system is not operational until you have carried out a calibration.
Additional functions associated with the switching unit are described in the documentation for
the switching unit, e.g. Nivotester FTL325N, FTL375N (for devices from Endress+Hauser).
BA299Fen016
Green LED 1 ( ready for operation), red LED 2 ( error indicated), yellow LED 3 (switching state)
6.4.1 Keys (A, B, C) on FEI58
To prevent unintentional operation of the device, approx. 2 seconds (s) have to elapse before the
system evaluates and executes a function commanded when a key is pressed (keys A and B). Test
key C disconnects the power supply immediately.
Both keys have to be pressed simultaneously to trigger switch point adjustment.
121 2
121 2
<20Hz< 20 Hz
60...185 Hz60...185 Hz
121 2
60...185 Hz60...185 Hz
ModeMode
InstrumentInstrument failurefailure
MaintenanceMaintenance
required *required *
Output signalOutput signal
Normal operationNormal operation
LEDsLEDs
green redgreen red
FEI58
NAMUR
-
IEC 60947-5-6
+
MIN
>2,2mA
MAX
C
1
2
GD E F
3
C
A B
LED
on
flashing
off
Key Function
A B C
X Display diagnostic code
X Display calibration situation
X X Perform calibration (during operation)
X X Delete calibration points (during startup)
X Test key , (disconnects the transmitter from the switching unit)