48
5.2.9.5 THD Settings
1. Press the SET button while Log Setup-THD is displayed.
2. Current option is displayed. Press the SET button again.
3. Select Active or Passive with UP/DOWN buttons. Press the SET button.
4. If you select Active option, recording time interval selection will be active.
5. At this stage, press the SET button again. The recording interval appears as 60 seconds.
6. Finish the selection by pressing the SET button.
7. When exiting from the menu with the BACK or ESC button, don’t forget to save the changes.
5.2.9.6 Activating Recording Function
To activate the recording function for any of the settings, select “ACTIVE” for any setting
At this point, recording interval will be selected. It can be selected as one of the following options:
1. 60 seconds
2. 300 seconds
3. 600 seconds
4. 900 seconds
5. 1200 seconds
6. 1800 seconds
7. 3600 seconds
5.2.9.7. Reading the Records via Modbus
There are two options for accesing the records via Modbus.