ProNet Series AC Servo User's Manual
- 143 -
Thus, the static inertia detection is complete.
NoteMake sure that the servomotor completes at least 6 full revolutions in the CCW direction before detection.
5.2.10 Absolute Encoder Multiturn Data and Alarm Reset
1. Press the MODE key to select the utility function mode.
2. Press the INC or DEC key to select the utility function number Fn010.
3. Press the ENTER key, the display will be shown as below.
4. Press the MODE key to reset the absolute encoder multiturn data and alarm.
5. Thus the absolute encoder multiturn data and alarm reset is complete.
Important:
This function will clear the absolute position of the encoder; the mechanical safety must be noted.
When the multiturn data is cleared, other encoder alarms will be reset at the same time.
5.2.11 Absolute Encoder Related Alarms Reset
1. Press the MODE key to select the utility function mode.
2. Press the INC or DEC key to select the utility function number Fn011.
3. Press the ENTER key, the display will be shown as below.
4. Press the MODE key to clear the alarms.
5. Thus the absolute encoder related alarms reset is complete.