The illustrations for this procedure show a two-post rack with narrow posts (3- to 5-inch) as an example.
The illustrations in the rack installation procedures are for reference only and may not show the actual device.
Complete the following tasks to install the device in a rack:
1. Attaching the front brackets to the device on page 32
2. Attaching the front brackets to the rack on page 33
3. Attaching the rear brackets to the rack on page 33
4. Attaching the rear brackets to the device on page 34
Attaching the front brackets to the device
Complete the following steps to attach the front brackets to the device.
1. Position the right front bracket with the
at side against the right side of the device, as shown in Figure 11.
2. Insert four 8-32 x 5/16-in. athead screws through the vertically aligned holes in the bracket and then into the holes on the
side of the device. Use the upper and lower screw holes, leaving the center holes empty.
3. Repeat step 1 and step 2 to attach the left front bracket to the left side of the device.
4. Tighten all the 8-32 x 5/16-in. screws to a torque of 15 in-lb (17 cm-kg).
FIGURE 11 Attaching the front brackets
1. The device
2. Front brackets, right and left
3. Screws, 8-32 x 5/16-in., athead Phillips
Installing the Universal Two-Post Rack Kit (XEN-R000294)
ExtremeSwitching SLX 9540 Hardware Installation Guide
32 9036360-00 Rev AB